TR002B | 20120125.0 www.vogelzang.com SHILOH™ | Page 7
Fig. 10 – Top View Minimum Clearance Dimensions
from Combustible Surfaces
1. The stove must be placed on solid concrete, solid
masonry, or when installed on a combustible floor,
on an UL 1618 Type 2 listed floor protector, such
as Hy-C or Imperial Model UL 3648BK (US) or
UL4048BK (CAN) or equivalent. Floor protec-
tor must be 1/2˝/13mm minimum thickness
(“k” value = 0.84, R value = 0.59, see page 24 for
calculation formulas) non-combustible material or
equivalent. US Requirements: The floor protector
must extend at least 16˝/41cm beyond the front
of the access door, 6˝/15.2cm to the sides and
12˝/30.5cm beyond the rear. Floor protection mate-
rial must extend under and 2˝/51mm beyond either
side of the stove pipe connector if it is elbowed
towards a wall. (See figures 10–12 and consult lo-
cal building codes and fire protection ordinances.)
Canadian Requirements: The base must extend
at least 18˝/46.8cm beyond the front of the access
door, 8˝/20.3cm to the sides, 8˝/20.3cm behind the
stove and must extend under and 2˝/51mm beyond
either side of the stove pipe if it is elbowed towards
a wall. (See figures 10–12 and consult local building
codes and fire protection ordinances).
CAUTION: (FIRE HAZARD) CARPETING AND
OTHER COMBUSTIBLE MATERIAL SHALL NOT
COVER THE FLOOR PROTECTOR. THESE MATE-
RIALS MUST REMAIN OUTSIDE OF COMBUS-
TIBLE CLEARANCES, SEE FIGURES 10 – 12.
2. The room in which he stove is installed must have
a minimum floor to ceiling height of 8 ft./2.4 m & a
minimum stove top to ceiling height of 55˝/140 cm.
3. The stove must have its own flue. Do not con-
nect this unit to a chimney flue serving other
appliances.
4. After observing the clearances to combus-
tible materials (figures 10–12), locate your floor
protector accordingly (figure 10) and care-
continued on next page
fully place the stove in your selected location.
Install stove pipe, elbows, and thimble as
required, utilizing either a recently cleaned and
inspected 6˝/152mm masonry chimney or a
6˝/152mm i.d. UL 103 HT (US)/ULC-S629 (CDN)
listed manufactured chimney.
5. Use round 6˝/152mm dia., minimum 24 MSG black
or 26 MSG blue steel stove pipe to connect the
stove to the chimney. DO NOT USE GALVANIZED
DUCT PIPE AS A CONNECTOR. Secure pipe
sections with three (3) sheet metal screws no more
than a maximum of 3˝/76mm apart in each stove
pipe and/or elbow joint to firmly hold the pipe sec-
tions together. DO NOT CONNECT THIS STOVE
TO ANY AIR DISTRIBUTION OR DUCT SYSTEM.
6. Recheck clearances from the stove,
connector stove pipe, and corner clearances
using the illustrations in figures 10–12 and
your local building codes or fire protection
ordinances.
NOTICE: Any wall containing combustible
materials such as wooden studs, drywall and
faced with brick or stone MUST be considered
a combustible surface.
7. DO NOT install this stove in a mobile home,
manufactured home, trailer or tent – NO
EXCEPTIONS! (HUD Federal Standard:
24 CFR Ch.xx)
8. The clearances provided are minimum dimensions
set by UL 1482-2010 & ULC-S627-00, tested and
applied by OMNI Test Laboratories, Inc., the manu-
facturer’s testing laboratory.
Clearances listed and shown MUST be adhered to
for safe operation of this appliance. CLEARANCES
MAY NOT BE REDUCED BY ANY MEANS IN USA
OR CANADA.
LOCATING STOVE
FLOOR
PROTECTOR
DASHED LINES SHOW HORIZONTAL CHIMNEY CONNECTOR
AND ADDITIONAL FLOOR PROTECTOR REQUIRED BENEATH
AND EXTENDING 2"/5cm BEYOND EACH SID
E
COMBUSTIBLE CONSTRUCTION IN ACCORDANCE WITH US NFPA 211
BACKWALL
SIDEWALL
8"/20.3cm
minimum
18"/46.8cm
44"/112cm
18"/46.8cm min.
8"/20.3cm min.
23"/54.5cm
15"/38.1cm
min.
12"/30.5cm
minimum
TOP VIEW | CANADIAN CLEARANCES
39"/
100cm
TR001B
Minimum
Clearances &
Minimum
Floor Protector
Dimensions
for Canadian
Installation
According to
ULC 5627
FLOOR
PROTECTOR
DASHED LINES SHOW HORIZONTAL CHIMNEY CONNECTOR
AND ADDITIONAL FLOOR PROTECTOR REQUIRED BENEATH
COMBUSTIBLE CONSTRUCTION IN ACCORDANCE WITH NFPA 211
BACKWALL
SIDEWALL
35"/
89cm
TR001B
18"/45.7cm
AND EXTENDING 2"/5cm BEYOND EACH SIDE
TOP VIEW | USA CLEARANCES
12"/30.5cm
minimum
12"/30.5cm
minimum
46"/117cm
Minimum
Clearances &
Minimum
Floor Protector
Dimensions
for United States
Installation
According to
UL 1482-2006
23"/54.5cm
15"/38.1cm
min.
6"/15.2cm min.
16"/40.6cm min.